In beta and available on request. The additions in this overview require the matching integration or controller update and are not confirmed as part of the standard customer release. Request them through your existing Eniris support conversation. The status applies to these additions, not to every existing function of the devices listed elsewhere on this page.
| Model / system | Beta addition | Validation and conditions |
|---|---|---|
| VGT Energy | Battery requests and installation-specific variants | In beta and available on request. Grid-perspective and behind-meter variants require matching commissioning. |
| VGT Energy grid-perspective feedback | Positive PV production for aggregate and individual-device active and executed power | In beta and available on request. Software regression tests and an ARM64 build passed for the PV sign correction. On-site validation is pending. Existing site-specific VGT functions must be retained in the selected update. |
| VGT Energy secondary SOC control | Configurable recharge power below the lower SOC bound | In beta and available on request. Offline calculation tests passed; on-site validation of the recharge-power addition is still pending. Requires the matching controller build. |
See integration details for connection requirements and operating limitations.
| Device Type | Variants | Supported |
|---|---|---|
| Solar Inverters | All | ✅) |
| Storage Devices | ✅ | |
| EV Chargers | ❌ |
This includes the SmartgridOne Controller Serial Number, and the SiteID, which is the same as the Serial Number with '_site_0' appended at the end.
In the next page, you have the option to include/exclude devices for remote control. Ensure to mark all checkboxes of devices you'd like to include.
When using multiple batteries, they are aggregated into one (virtual) asset.
'VGT Energy' is now set up on the SmartgridOne Controller.
PV feedback remains positive in grid-perspective reporting. Battery requests no longer unnecessarily curtail PV. Secondary SOC control can use a separate recharge-power limit below its lower SOC bound. Installation-specific behind-the-meter variants require matching commissioning; they are not interchangeable with grid-perspective control.
The beta correction keeps PV production positive in both aggregate and individual-device feedback, including active and executed power. Battery charging remains negative and battery discharging remains positive. The PV correction has passed software regression tests and an ARM64 build; it has not yet been validated on a customer installation. Installations using a specific VGT controller version require a compatibility check that retains their existing battery, state-of-charge and peak-shaving behaviour. The matching update is installed only within a confirmed execution window.
With the matching beta controller build, Recharge power (kW) below the lower SoC bound sets the recharge power used when no external call is active. Leave it empty to retain full-power recharge. A value of 20 kW requests 20 kW of battery charging, or the available PV surplus if that is higher, capped at the battery's maximum charge power. A value of 0 uses PV surplus only. The setting does not cap total site import, other site loads or the power requested by an external call. The existing lower and upper SOC bounds remain in effect. This addition has passed offline calculation tests; physical recharge validation is still pending. Installation and testing require an agreed execution window with Eniris.