This guide will serve as a guide to adjust the Alfen charging station settings to allow communication with and control by the SmartgridOne Controller. For more in depth information you can use the Alfen Smart charging implementation guide
In beta and available on request. The additions in this overview require the matching integration or controller update and are not confirmed as part of the standard customer release. Request them through your existing Eniris support conversation. The status applies to these additions, not to every existing function of the devices listed elsewhere on this page.
| Model / system | Beta addition | Validation and conditions |
|---|---|---|
| Alfen Eve Single / Eve S-line, one socket, Modbus TCP unit ID 1 | Monitoring while an external EMS owns charging, with no SmartgridOne Modbus writes in control or release paths | In beta and available on request. Live measurements and no-write command paths verified on two stations at rest; an active charging session with this variant remains to be checked. Battery hold is a separate configuration and is not included or validated by this driver alone. |
| Alfen NG9xx / Eve | Repeated current limits and release commands | Select the actual connector arrangement |
| Alfen NG910 | Single-/three-phase requests | Register writes checked; physical phase switching pending |
| Alfen NG9xx (single socket, Modbus TCP unit ID 1) | Current limit without the applied-current feedback check, so the notice "Setpoint rejected by device(s)" no longer appears while the station follows the limit (for example at the 6 A minimum) | Measurements, Mode 3 state, energy counter and limit commands verified on an installation, including a charging session in which the measured power followed the EMS limit and no rejection notice appeared at the 6 A minimum; a long session at the minimum current has not yet been observed |
See integration details for connection requirements and operating limitations.
| Device Type | Modbus TCP (Ethernet) | RS485 | Instruction video |
|---|---|---|---|
| Most Alfen charging stations | ✅ | ❌ |
Install the charging station.
Update the Alfen charging station to firmware version 4.2.0 (or higher).
Connect the Alfen charging station to a network with the following requirements:
Install the ACE service installer tool, or search for the latest version of the ACE service installer on the internet if the link does not work.
Create a valid account for Alfen ACE Service Installer now (to be requested via https://support.alfen.com)
To control the charging station, the smart charging functionality must first be purchased and then rolled out.
Unlocking functionality via the ACE Service Installer: to unlock functionality via the ACE Service Installer, do the following:
Open the ACE Service Installer
Click on the desired charging station
Go to the General info tab and select License key
Click Update license key to activate the purchased functionality. The charging station will restart after the license key is updated.
If the location has a weak internet connection, the following procedure can be used to unlock the desired functionality:
Open the ACE Service Installer
Go to Device in the menu
Select Install feature(s)
Enter the license key and click OK. The charging station will restart after the license key is updated.
Configuring ALB via the ACE Service Installer
Open the ACE Service Installer
Select the charging station
Select the Smart Charging tab
Check the box next to Active load balancing. The following parameters are displayed.
Data Source; enter the data source type:
Enter the Safe current. This is the current limit the charging station uses when the connection between the charging station and the energy meter/Energy Management System is lost.
If permitted, enter the phase rotation. Note: This is the phase sequence of the power cable (to the charging station). There are several options depending on the type of charging station and connection.
Click Save
Click the power button to restart the charging station.
Configuring an EMS via the ACE Service Installer
If the Energy Management System is selected as the data source (see step 6: "Configuring ALB via the ACE Service Installer"), an additional page will appear on the screen. Double-click to open the screen. Select TCP/IP EMS in the menu.
Enter the mode. Select whether the EMS manages each individual socket or an entire Smart Charging Network.
Enter the validity period (default 60 s). If the charging station has not received updates from the EMS within the configured validity period, it will interpret this as a disconnection and will return to the configured safe current.
Test the connection of a ALB with a EMS
Configure the installation according to the instructions in the previous steps.
Go to the Live Monitoring tab, select States, and observe the Modbus TCP/IP connection status as shown below:
If this status is Not in use (communication idle), there is a loss of communication. Check your installation or consult the Troubleshooting section for more information.
Connect a vehicle and start a charging session.
Use the EMS to change the maximum available power. The method for doing this varies by EMS. Consult the EMS manufacturer's manual for more information.
Go to the Live Monitoring tab, select Currents, and view the currents being drawn.
Custom variants repeat charging-current limits and release commands where required. An NG910 variant adds one-/three-phase requests; register writes have been verified, while vehicle-specific physical phase switching still needs commissioning. Select the variant for the actual connector configuration.
In beta and available on request. This variant controls one socket at Modbus TCP unit ID 1. It reads the voltages, currents, active and reactive power per phase, the frequency and the Mode 3 state of the socket, and writes the EMS charge current limit (6 to 32 A, 0 A to pause when pausing is allowed in the device settings) every 20 seconds, within the validity period of the station. It does not compare the applied maximum current of the station with the requested limit afterwards. Use it when the station follows the limit but the controller still shows "Setpoint rejected by device(s)". The station must be configured with Energy Management System as data source, as described above. The Mode 3 state is read as one block of five registers, as the station requires. The station's own product identification (serial number) is not read in this variant.
In beta and available on request. A monitoring-only custom variant reads the station voltages, frequency, power, connector currents, Mode 3 state and energy counter over Modbus TCP, unit ID 1. Its control and release paths perform no register writes, including after a driver restart. The external charging EMS remains responsible for the current limit, tariff schedule, load balancing and communication watchdog. This variant must not be used to control charging from SmartgridOne.
The connector remains in the scheduler model so its existing battery-exclusion setting can be retained; a successful scheduler command in a diagnostic view does not mean a current command was sent to the station. Keep the verified nominal ratings configured. Holding the battery throughout an external charging session requires a separate, site-specific control rule and verification during real charging. The monitoring variant alone does not guarantee battery hold, stop charging or take over load balancing. Do not replace the external EMS watchdog or safe-current settings with SmartgridOne control instructions when using this variant.