In beta and available on request. The additions in this overview require the matching integration or controller update and are not confirmed as part of the standard customer release. Request them through your existing Eniris support conversation. The status applies to these additions, not to every existing function of the devices listed elsewhere on this page.
| Model / system | Beta addition | Validation and conditions |
|---|---|---|
| NexBlue Edge Max | Avoid reserved and undefined registers | Field-validated on one installation (charger firmware 03.09.97). Requires the matching controller update |
| NexBlue Edge Max | Current control while OCPP is active (for example a charge point operator backend) | Software-tested; not yet field-validated with OCPP active. Requires the matching controller update |
See integration details for connection requirements and operating limitations.
| Device Type | Modbus TCP (Ethernet) | RS485 |
|---|---|---|
| Edge 2 | ✅ | ❌ |
| Edge Max | ||
| Delta | ||
| Delta Max |
For general Ethernet wiring best practices, see the Ethernet wiring guidelines.
Polling avoids reserved and undefined input registers that can cause Modbus exceptions. The charging status is read once per cycle.
When OCPP is active on the charger, for example because it is connected to a charge point operator backend, NexBlue does not accept Modbus start and stop commands. Charging sessions are then started and stopped through OCPP (charge card or app). With this addition the Controller keeps adjusting the charging current over Modbus TCP and pauses charging with a current limit of 0 A, which does not end the OCPP transaction. When OCPP is switched off again, the Controller resumes Modbus start and stop within about 10 minutes.
Modbus TCP must remain enabled on the charger.