The SmartgridOne Controller supports Kostal Pico inverters that use the "Kostal Pico protocol". This includes many inverters from the PIKO series.
| Device Type | Modbus TCP (Ethernet) | RS485 | Curtailment |
|---|---|---|---|
| Kostal Pico Inverters | ✅ | ✅ | ❌ |
Curtailment While these inverters support active power control and feed-in limitation, the protocol driver used by the SmartgridOne Controller does not currently support sending curtailment commands.
Kostal inverters can be connected to the SmartgridOne Controller via Modbus TCP (Ethernet) or RS485.
The default RS485 bus address is often 1. If you have more than one inverter on the bus, you must assign a unique address to each one. This can typically be done via the inverter's display menu or web server.
The physical RS485 connection varies by inverter model. Please consult your specific inverter's installation manual for the correct terminals and pinout.
Connect the inverter's RS485 terminals to the SmartgridOne Controller as follows:
| Device | SmartgridOne Controller model OM1 | SmartgridOne Controller model IG8 | RS485-USB converter | RS485-Ethernet converter |
|---|---|---|---|---|
| Data A | RS485 A | RS485_POS | RS485 A | TX+ |
| Data B | RS485 B | RS485_NEG | RS485 B | TX- |
| Ground | RS GND | GND | Not available | G |