weiheng EMS100

In beta and available on request. The additions in this overview require the matching integration or controller update and are not confirmed as part of the standard customer release. Request them through your existing Eniris support conversation. The status applies to these additions, not to every existing function of the devices listed elsewhere on this page.
| Model / system | Beta addition | Validation and conditions |
|---|---|---|
| Weiheng EMS100 | Correct millivolt scale for BMS cell voltage | Protocol and seven decoder regression tests passed. On-controller measurements confirmed maximum 3.331 V and minimum/average 3.329 V with unchanged 372.9 V pack voltage. Charging and discharging are separate checks |
See integration details for connection requirements and operating limitations.
| Device Type | Modbus TCP (Ethernet) | RS485 | Curtailment | Reactive power control |
|---|---|---|---|---|
| EMS100 | ✅ | ❌ | ⚠️ | — |
Weiheng EMS100 Modbus TCP502Make sure the Controller and the Weiheng EMS100 are connected to the same network.
For correct ethernet wiring: Follow the the guidelines for ethernet wiring.
⚠️ Make sure the device Direct power control read-only mode is off. If it is on we can't send commands with the EMS100.
⚠️ Please also note that the Intelligent mode should be on, and this can be enabled by the PANGU OS.
BMS single-cell voltage readings use the millivolt scale of EMS100 protocol V2: input registers 6557 (maximum), 6558 (minimum) and 6565 (average) use 0.001 V per count. For example, 3331 represents 3.331 V. The update retains the existing measurement fields and node identities, and does not change the actual cell voltage, protection thresholds or control settings. On-controller measurements on 11 November 2026 confirmed 3.331 V maximum and 3.329 V minimum/average after the update, while the 372.9 V pack measurement remained unchanged. This validates the measurement correction; it does not establish charging or discharging performance.