In beta and available on request. The additions in this overview require the matching integration or controller update and are not confirmed as part of the standard customer release. Request them through your existing Eniris support conversation. The status applies to these additions, not to every existing function of the devices listed elsewhere on this page.
| Model | Connection and beta support | Physical validation and conditions |
|---|---|---|
| AIO-H3-6.0 (6 kW) | RS485 local AC-power control driver. In beta and available on request. | Charging from idle, stopping the manual test, and discharge above minimum SOC physically verified on the idle-start revision. Self Use mode is required; BMS, SOC, current and site limits remain active. Other AIO ratings and firmware combinations require separate verification. |
| Model / system | Beta addition | Validation and conditions |
|---|---|---|
| FoxESS H3 Plus / RVH3+ | Separate protocol implementation candidates | Technical assessment and physical control validation required |
See integration details for connection requirements and operating limitations.
| Device Type | Modbus TCP (Ethernet) | RS485 | Curtailment | Reactive power control | Minimum device firmware version |
|---|---|---|---|---|---|
| H3 (Non-Pro, Non-Smart): → ❗See note below ❗ | ❌ | ✅ | ❗(see below) | — | Master: 2.05, Manager: 1.85 (*) |
| H3 AIO (All-In-One) | ✅ | ❌ | Master: 1.33, Manager: 1.37 (*) | ||
| H3-Smart | ⌛ (in development) | Master: 1.25, Manager: 1.14 (*) | |||
| H3-Pro | Master: 1.62, Manager: 1.34 (*) | ||||
| H1 | (experimental, requires testing) | Master: 1.70, Manager: 1.78 (*) | |||
| H1-G2 | ⌛ (in development) | Master: 1.40, Manager: 1.54 (*) | |||
| P3-SH | ✅ (experimental) | ✅ (experimental) | Master: 1.62, Manager: 1.34 (*) |
The H3 (Non-Pro, Non-Smart) has different communication protocol depending on the inverter 'master version' and 'manager version'. Choose the corresponding integration based on the inverter's software versions.
✅ Curtailment is supported for Firmware versions master v.2.05 and manager v.1.85 and below.
⌛ Curtailment is in development for Firmware versions master v.2.06 and manager v.1.86 and above.
The H3 (non-pro, non-smart) series uses a different communication protocol than the H3 Pro and H3 Smart series. Therefore, when selecting the device type in the SmartgridOne Controller, you must be very sure that you select the correct type.
(*) The integration may work for older firmware versions, but these are not tested.
The default modbus address, or device ID, is 247. Keep this in mind when scanning for an inverter. You can change the minimum and maximum bus addresses the controller will scan in the scan parameters.
For correct ethernet wiring: Follow the the guidelines for ethernet wiring.
You cannot connect it through the WiFi dongle.
The inverter can be connected to the SmartgridOne Controller via RS485. This is done through connection [J] in the image below.
| Device | SmartgridOne Controller model OM1 | SmartgridOne Controller model IG8 | RS485-USB converter | RS485-Ethernet converter |
|---|---|---|---|---|
| Logger 485A / pin 1 | RS485 A | RS485_POS | RS485 A | TX+ |
| Logger 485B / pin 2 | RS485 B | RS485_NEG | RS485 B | TX- |
| N/A | RS GND | GND | Not available | G |
| Device | SmartgridOne Controller model OM1 | SmartgridOne Controller model IG8 | RS485-USB converter | RS485-Ethernet converter |
|---|---|---|---|---|
| EMS 485A / pin 17 | RS485 A | RS485_POS | RS485 A | TX+ |
| EMS 485B / pin 18 | RS485 B | RS485_NEG | RS485 B | TX- |
| N/A | RS GND | GND | Not available | G |
The control must be activated through the inverter, and the meter must be deactivated. This is done through the display in the Feature Parm menu. First, open the Feature Parm menu as follows:
Use the display further from the Feature page to activate the control, following the steps below:
The meter must be deactivated. The control will be taken over by the SmartgridOne Controller. Therefore, the meter should not be connected to the inverter but to the SmartgridOne Controller. To deactivate the meter in the settings, follow these steps:
The address of the inverter can also be set through the display.
The SmartgridOne Controller starts scanning from address 1 by default. Choosing a lower address will make your inverter be found faster.
If you have multiple inverters then it is important to set the parallel addresses, each inverter should have a different address.
Remote control is activated by default, you do not need to change any settings.
Changing the inverter address (or device ID) can be done in the smae way as the H3 (see above).
An earlier implemented candidate remains available for technical assessment on request. Its earlier review was closed; Eniris must review and prepare the appropriate version before installation. It is not a ready-to-install standard release. Separate H3 Plus / RVH3+ protocol implementation candidates exist. Their presence does not establish support for other FoxESS families or firmware. Exact register mapping, power control and physical behaviour require verification.
In beta and available on request. A local custom Modbus driver is available for AIO-H3-6.0 AC-power control over RS485. It retains the existing inverter, PV and battery measurements and node history. It uses the AIO-H3 protocol of 10 July 2022, single-register remote enable with readback and signed 32-bit AC power commands. The inverter must be in Self Use mode. The idle-start revision accepts the normal Idle and On-grid states and retains the separate BMS, SOC, voltage, current and power checks. It does not enable operation in EPS or fault states.
Charging from idle and discharge above the existing minimum SOC were physically verified on an AIO-H3-6.0 with this revision. Manual test overrides were stopped after each test. This beta is not a general firmware compatibility claim and does not establish independent PV curtailment. Request the appropriate driver and installation assessment through your existing Eniris support conversation.