| Device Type | Modbus TCP (Ethernet) | RS485 | Curtailment |
|---|---|---|---|
| WH-THA502 | ❌ | ✅ | ⚠️ |
| WH-THA602 | |||
| WH-THA802 | |||
| WH-THA103 | |||
| WH-THA123 | |||
| WH-THA133 |
WHES Three Phase Hybrid Inverter Protocol (RTU)The SmartgridOne Controller communicates with this device over Modbus RTU on RS485. This device has no Modbus TCP interface, so an Ethernet connection cannot be used.
Run the communication cable directly from the VPP 485 port of the device to an RS485 port on the SmartgridOne Controller.
| Device | SmartgridOne Controller model OM1 | SmartgridOne Controller model IG8 | RS485-USB converter | RS485-Ethernet converter |
|---|---|---|---|---|
| VPP_485A | RS485 A | RS485_POS | RS485 A | TX+ |
| VPP_485B | RS485 B | RS485_NEG | RS485 B | TX- |
| N/A | RS GND | GND | Not available | G |
The SmartgridOne Controller supports only these serial settings for this device:
| Setting | Value |
|---|---|
| Protocol | Modbus RTU |
| Baud rate | 115200 |
| Parity | None |
| Data bits | 8 |
| Stop bits | 1 |
| Modbus address | 1 (default), 1 - 247 supported |